STU Status LED Meanings
The status of the 3GSTU is indicated on the LEDs in priority order - highest first.
Where a high priority condition exists, it is indicated on the LED and suppresses
the indication of lower priority conditions.
For example, if a battery low condition is present, battery low is indicated on the
red LED regardless of the state of AC Fail.
Green flutter flash for
2
/
3
s:
Transmitting or receiving alarm data over landline (chirp).
Green fast flash:
Battery power is low. Battery low is indicated on the LED as soon as it is
detected. The battery low alarm is only transmitted after a delay.
Green slow flash:
The STU has been commissioned by the ARC.
Green permanently off:
STU is not powered.
Red permanently off:
Normal
Red fast flash:
The STU has detected an NVM configuration error.
Red flutter flash:
STU has one or more alarms or openings/closings present.
The LED flashes once for each unacknowledged alarm on pins 1 to 8 (1 to 11 for
11zstu) and is then off for a few seconds.
SYSTEM COMMISSIONING
Note 1: The STU should not be commissioned if a data device is busy using the
telephone line.
Note 2: If an MCD is fitted it will disconnect the telephone or data device
connected through it during commissioning.
Apply power to the alarm panel and the STU and observe the status indicators.
The red and green LEDs will slow flash together (on for 2.5 seconds approx. and
off for 2.5 seconds approx.).